Multi-Triple
|
Criteria |
Standard Values |
Unit |
||||
Conductor cross section |
Nominal |
0.5 |
0.75 |
1 |
1.5 |
2.5 |
mm² |
Conductor DC Resistance @ 20oC |
max. |
36.7 |
25.0 |
18.5 |
12.3 |
7.4 |
Ohm/kM |
Insulation resistance |
min. |
100 |
MOhm x km |
||||
Mutual capacitance |
max. |
250 |
nF/km |
||||
L/R (ratio) |
max. |
25 |
25 |
25 |
40 |
60 |
microH/Ohm |
Test voltage : |
for 1 minute |
2.0 kV A.C or 3.0 kV D.C |
K.V |
||||
core to core |
|||||||
core to screen |
|||||||
Operating voltage U(rms) |
|
500 |
V |
Nominal cross section area of conductor |
Insulation thickness |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 0.5 mm2 (7x0.3 mm) |
|||||
1x3x0.5 |
0.6 |
0.9 |
6.6 |
55 |
1000 |
2x3x0.5 |
0.6 |
1.0 |
10.1 |
98 |
1000 |
3x3x0.5 |
0.6 |
1.0 |
10.8 |
127 |
1000 |
4x3x0.5 |
0.6 |
1.0 |
11.8 |
158 |
1000 |
5x3x0.5 |
0.6 |
1.1 |
13.1 |
195 |
1000 |
6x3x0.5 |
0.6 |
1.1 |
14.3 |
227 |
1000 |
7x3x0.5 |
0.6 |
1.1 |
14.3 |
253 |
1000 |
10x3x0.5 |
0.6 |
1.2 |
18.4 |
359 |
1000 |
12x3x0.5 |
0.6 |
1.2 |
19.0 |
415 |
1000 |
16x3x0.5 |
0.6 |
1.3 |
21.3 |
541 |
1000 |
20x3x0.5 |
0.6 |
1.4 |
24.0 |
670 |
1000 |
24x3x0.5 |
0.6 |
1.5 |
26.8 |
802 |
500 |
30x3x0.5 |
0.6 |
1.5 |
28.4 |
971 |
500 |
Conductor : 0.75 mm2 (7x0.37 mm) |
|||||
1x3x0.75 |
0.6 |
0.9 |
7.1 |
66 |
1000 |
2x3x0.75 |
0.6 |
1.0 |
10.9 |
120 |
1000 |
3x3x0.75 |
0.6 |
1.0 |
11.6 |
159 |
1000 |
4x3x0.75 |
0.6 |
1.1 |
12.9 |
205 |
1000 |
5x3x0.75 |
0.6 |
1.1 |
14.1 |
246 |
1000 |
6x3x0.75 |
0.6 |
1.1 |
15.4 |
288 |
1000 |
7x3x0.75 |
0.6 |
1.1 |
15.4 |
324 |
1000 |
10x3x0.75 |
0.6 |
1.3 |
20.2 |
468 |
1000 |
12x3x0.75 |
0.6 |
1.3 |
20.8 |
543 |
1000 |
16x3x0.75 |
0.6 |
1.4 |
23.4 |
708 |
1000 |
20x3x0.75 |
0.6 |
1.5 |
26.3 |
878 |
500 |
24x3x0.75 |
0.6 |
1.6 |
29.4 |
1050 |
500 |
30x3x0.75 |
0.6 |
1.6 |
31.2 |
1277 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 1.0 mm2 (7x0.43 mm) |
|||||
1x3x1 |
0.6 |
0.9 |
7.5 |
76 |
1000 |
2x3x1 |
0.6 |
1.0 |
11.6 |
141 |
1000 |
3x3x1 |
0.6 |
1.0 |
12.3 |
189 |
1000 |
4x3x1 |
0.6 |
1.1 |
13.7 |
244 |
1000 |
5x3x1 |
0.6 |
1.1 |
15.0 |
295 |
1000 |
6x3x1 |
0.6 |
1.2 |
16.6 |
353 |
1000 |
7x3x1 |
0.6 |
1.2 |
16.6 |
398 |
1000 |
10x3x1 |
0.6 |
1.3 |
21.5 |
564 |
1000 |
12x3x1 |
0.6 |
1.3 |
22.2 |
658 |
1000 |
16x3x1 |
0.6 |
1.4 |
25.0 |
861 |
500 |
20x3x1 |
0.6 |
1.5 |
28.1 |
1068 |
500 |
24x3x1 |
0.6 |
1.6 |
31.4 |
1279 |
500 |
30x3x1 |
0.6 |
1.7 |
33.5 |
1574 |
500 |
Conductor : 1.5 mm2 (7x0.53 mm) |
|||||
1x3x1.5 |
0.6 |
0.9 |
8.1 |
97 |
1000 |
2x3x1.5 |
0.6 |
1.1 |
12.9 |
187 |
1000 |
3x3x1.5 |
0.6 |
1.1 |
13.7 |
254 |
1000 |
4x3x1.5 |
0.6 |
1.1 |
15.1 |
323 |
1000 |
5x3x1.5 |
0.6 |
1.2 |
16.8 |
399 |
1000 |
6x3x1.5 |
0.6 |
1.2 |
18.3 |
470 |
1000 |
7x3x1.5 |
0.6 |
1.2 |
18.3 |
532 |
1000 |
10x3x1.5 |
0.6 |
1.4 |
23.9 |
766 |
1000 |
12x3x1.5 |
0.6 |
1.4 |
24.8 |
896 |
500 |
16x3x1.5 |
0.6 |
1.5 |
27.8 |
1174 |
500 |
20x3x1.5 |
0.6 |
1.6 |
31.3 |
1458 |
500 |
24x3x1.5 |
0.6 |
1.7 |
35.0 |
1746 |
500 |
30x3x1.5 |
0.6 |
1.8 |
37.3 |
2152 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 2.5 mm2 (7x0.67 mm) |
|||||
1x3x2.5 |
0.7 |
1.0 |
9.7 |
141 |
1000 |
2x3x2.5 |
0.7 |
1.1 |
15.2 |
269 |
1000 |
3x3x2.5 |
0.7 |
1.2 |
16.4 |
378 |
1000 |
4x3x2.5 |
0.7 |
1.2 |
18.1 |
484 |
1000 |
5x3x2.5 |
0.7 |
1.3 |
20.1 |
599 |
1000 |
6x3x2.5 |
0.7 |
1.4 |
22.2 |
716 |
1000 |
7x3x2.5 |
0.7 |
1.4 |
22.2 |
813 |
1000 |
10x3x2.5 |
0.7 |
1.6 |
29.0 |
1167 |
500 |
12x3x2.5 |
0.7 |
1.6 |
30.0 |
1369 |
500 |
16x3x2.5 |
0.7 |
1.7 |
33.6 |
1795 |
500 |
20x3x2.5 |
0.7 |
1.9 |
38.0 |
2244 |
500 |
24x3x2.5 |
0.7 |
2.0 |
42.5 |
2685 |
500 |
30x3x2.5 |
0.7 |
2.1 |
45.3 |
3310 |
500 |

|