Multi-Pair
|
Criteria |
Standard Values |
Unit |
||||
Conductor cross section |
Nominal |
0.5 |
0.75 |
1 |
1.5 |
2.5 |
mm² |
Conductor DC Resistance @ 20oC |
max. |
36.7 |
25.0 |
18.5 |
12.3 |
7.4 |
Ohm/kM |
Insulation resistance |
min. |
1000 |
MOhm x km |
||||
Mutual capacitance |
max. |
150 |
nF/km |
||||
Capacitance unbalance |
max. |
500 |
pF/500m |
||||
L/R (ratio) |
max. |
25 |
25 |
25 |
40 |
60 |
microH/Ohm |
Test voltage : |
for 1 minute |
2.0 kV A.C or 3.0 kV D.C |
K.V |
||||
core to core |
|||||||
core to screen |
|||||||
Operating voltage U(rms) |
|
500 |
V |
Nominal cross section area of conductor |
Insulation thickness |
Armour Tape Thickness |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 0.5 mm2 (7x0.30 mm) |
|||||||
1x2x0.5 |
0.6 |
0.2 |
7.4 |
1.3 |
10.8 |
165 |
1000 |
2x2x0.5 |
0.6 |
0.2 |
10.8 |
1.4 |
14.4 |
246 |
1000 |
3x2x0.5 |
0.6 |
0.2 |
11.4 |
1.4 |
15.0 |
277 |
1000 |
4x2x0.5 |
0.6 |
0.2 |
12.5 |
1.4 |
16.1 |
315 |
1000 |
5x2x0.5 |
0.6 |
0.2 |
13.7 |
1.4 |
17.3 |
355 |
1000 |
6x2x0.5 |
0.6 |
0.2 |
15.0 |
1.5 |
18.8 |
403 |
1000 |
7x2x0.5 |
0.6 |
0.2 |
15.0 |
1.5 |
18.8 |
423 |
1000 |
10x2x0.5 |
0.6 |
0.2 |
19.2 |
1.5 |
23.0 |
555 |
1000 |
12x2x0.5 |
0.6 |
0.2 |
19.9 |
1.6 |
23.9 |
614 |
1000 |
16x2x0.5 |
0.6 |
0.2 |
22.2 |
1.6 |
26.2 |
732 |
500 |
20x2x0.5 |
0.6 |
0.2 |
24.8 |
1.7 |
29.0 |
867 |
500 |
24x2x0.5 |
0.6 |
0.2 |
27.7 |
1.7 |
31.9 |
996 |
500 |
30x2x0.5 |
0.6 |
0.2 |
29.4 |
1.7 |
33.6 |
1143 |
500 |
Conductor : 0.75 mm2 (7x0.37 mm) |
|||||||
1x2x0.75 |
0.6 |
0.2 |
7.9 |
1.3 |
11.3 |
179 |
1000 |
2x2x0.75 |
0.6 |
0.2 |
11.4 |
1.4 |
15.0 |
271 |
1000 |
3x2x0.75 |
0.6 |
0.2 |
12.2 |
1.4 |
15.8 |
309 |
1000 |
4x2x0.75 |
0.6 |
0.2 |
13.4 |
1.4 |
17.0 |
355 |
1000 |
5x2x0.75 |
0.6 |
0.2 |
14.6 |
1.5 |
18.4 |
410 |
1000 |
6x2x0.75 |
0.6 |
0.2 |
16.0 |
1.5 |
19.8 |
459 |
1000 |
7x2x0.75 |
0.6 |
0.2 |
16.0 |
1.5 |
19.8 |
484 |
1000 |
10x2x0.75 |
0.6 |
0.2 |
20.6 |
1.6 |
24.6 |
651 |
500 |
12x2x0.75 |
0.6 |
0.2 |
21.3 |
1.6 |
25.3 |
714 |
500 |
16x2x0.75 |
0.6 |
0.2 |
23.8 |
1.6 |
27.8 |
860 |
500 |
20x2x0.75 |
0.6 |
0.2 |
26.7 |
1.7 |
30.9 |
1024 |
500 |
24x2x0.75 |
0.6 |
0.2 |
29.7 |
1.8 |
34.1 |
1194 |
500 |
30x2x0.75 |
0.6 |
0.2 |
31.6 |
1.8 |
36.0 |
1380 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Tape Thickness |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 1.0 mm2 (7x0.43 mm) |
|||||||
1x2x1 |
0.6 |
0.2 |
8.2 |
1.3 |
11.6 |
191 |
1000 |
2x2x1 |
0.6 |
0.2 |
12.0 |
1.4 |
15.6 |
293 |
1000 |
3x2x1 |
0.6 |
0.2 |
12.8 |
1.4 |
16.4 |
337 |
1000 |
4x2x1 |
0.6 |
0.2 |
14.1 |
1.4 |
17.7 |
390 |
1000 |
5x2x1 |
0.6 |
0.2 |
15.4 |
1.5 |
19.2 |
452 |
1000 |
6x2x1 |
0.6 |
0.2 |
16.9 |
1.5 |
20.7 |
509 |
1000 |
7x2x1 |
0.6 |
0.2 |
16.9 |
1.5 |
20.7 |
541 |
1000 |
10x2x1 |
0.6 |
0.2 |
21.8 |
1.6 |
25.8 |
730 |
500 |
12x2x1 |
0.6 |
0.2 |
22.6 |
1.6 |
26.6 |
806 |
500 |
16x2x1 |
0.6 |
0.2 |
25.2 |
1.7 |
29.4 |
989 |
500 |
20x2x1 |
0.6 |
0.2 |
28.2 |
1.7 |
32.4 |
1170 |
500 |
24x2x1 |
0.6 |
0.2 |
31.5 |
1.8 |
35.9 |
1367 |
500 |
30x2x1 |
0.6 |
0.2 |
33.5 |
1.8 |
37.9 |
1591 |
500 |
Conductor : 1.5 mm2 (7x0.53 mm) |
|||||||
1x2x1.5 |
0.6 |
0.2 |
8.8 |
1.3 |
12.2 |
213 |
1000 |
2x2x1.5 |
0.6 |
0.2 |
13.0 |
1.4 |
16.6 |
334 |
1000 |
3x2x1.5 |
0.6 |
0.2 |
13.9 |
1.4 |
17.5 |
392 |
1000 |
4x2x1.5 |
0.6 |
0.2 |
15.3 |
1.5 |
19.1 |
467 |
1000 |
5x2x1.5 |
0.6 |
0.2 |
16.8 |
1.5 |
20.6 |
536 |
1000 |
6x2x1.5 |
0.6 |
0.2 |
18.4 |
1.5 |
22.2 |
607 |
1000 |
7x2x1.5 |
0.6 |
0.2 |
18.4 |
1.5 |
22.2 |
650 |
1000 |
10x2x1.5 |
0.6 |
0.2 |
23.7 |
1.6 |
27.7 |
884 |
500 |
12x2x1.5 |
0.6 |
0.2 |
24.6 |
1.7 |
28.8 |
996 |
500 |
16x2x1.5 |
0.6 |
0.2 |
27.5 |
1.7 |
31.7 |
1221 |
500 |
20x2x1.5 |
0.6 |
0.2 |
30.9 |
1.8 |
35.3 |
1467 |
500 |
24x2x1.5 |
0.6 |
0.2 |
34.5 |
1.9 |
39.1 |
1720 |
500 |
30x2x1.5 |
0.6 |
0.2 |
37.1 |
1.9 |
41.7 |
2059 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Tape Thickness |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 2.5 mm2 (7x0.67 mm) |
|||||||
1x2x2.5 |
0.7 |
0.2 |
10.1 |
1.4 |
13.7 |
263 |
1000 |
2x2x2.5 |
0.7 |
0.2 |
15.0 |
1.5 |
18.8 |
424 |
1000 |
3x2x2.5 |
0.7 |
0.2 |
16.1 |
1.5 |
19.9 |
506 |
1000 |
4x2x2.5 |
0.7 |
0.2 |
17.7 |
1.5 |
21.5 |
601 |
1000 |
5x2x2.5 |
0.7 |
0.2 |
19.5 |
1.6 |
23.5 |
707 |
1000 |
6x2x2.5 |
0.7 |
0.2 |
21.4 |
1.6 |
25.4 |
807 |
500 |
7x2x2.5 |
0.7 |
0.2 |
21.4 |
1.6 |
25.4 |
871 |
500 |
10x2x2.5 |
0.7 |
0.2 |
27.8 |
1.8 |
32.2 |
1207 |
500 |
12x2x2.5 |
0.7 |
0.2 |
28.8 |
1.8 |
33.2 |
1356 |
500 |
16x2x2.5 |
0.7 |
0.2 |
32.3 |
1.9 |
36.9 |
1694 |
500 |
20x2x2.5 |
0.7 |
0.2 |
36.7 |
2.0 |
41.5 |
2086 |
500 |
24x2x2.5 |
0.7 |
0.5 |
41.0 |
2.1 |
47.2 |
2941 |
500 |
30x2x2.5 |
0.7 |
0.5 |
43.6 |
2.1 |
49.8 |
3413 |
500 |

|