Multi-Pair
|
Criteria |
Standard Values |
Unit |
||||
Conductor cross section |
Nominal |
0.5 |
0.75 |
1 |
1.5 |
2.5 |
mm² |
Conductor DC Resistance @ 20oC |
max. |
40.4 |
26 |
19.2 |
12.8 |
7.86 |
Ohm/kM |
Insulation resistance |
min. |
1000 |
MOhm x km |
||||
Mutual capacitance |
max. |
150 |
nF/km |
||||
L/R (ratio) |
max. |
25 |
25 |
25 |
40 |
60 |
microH/Ohm |
Test voltage : |
for 5 minutes |
1.5 kV A.C |
K.V |
||||
core to core |
|||||||
core to screen |
|||||||
Operating voltage U(rms) |
|
300 |
V |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 0.5 mm2 (7x0.30 mm) |
|||||||
1x2x0.5 |
0.4 |
0.2 |
5.7 |
1.1 |
8.8 |
118 |
1000 |
2x2x0.5 |
0.4 |
0.2 |
7.9 |
1.2 |
11.2 |
164 |
1000 |
3x2x0.5 |
0.4 |
0.2 |
8.3 |
1.2 |
11.6 |
182 |
1000 |
4x2x0.5 |
0.4 |
0.2 |
9.0 |
1.2 |
12.3 |
209 |
1000 |
5x2x0.5 |
0.4 |
0.2 |
9.8 |
1.2 |
13.1 |
230 |
1000 |
6x2x0.5 |
0.4 |
0.3 |
10.7 |
1.3 |
14.6 |
288 |
1000 |
7x2x0.5 |
0.4 |
0.3 |
10.7 |
1.3 |
14.6 |
301 |
1000 |
10x2x0.5 |
0.4 |
0.3 |
13.4 |
1.4 |
17.6 |
395 |
1000 |
12x2x0.5 |
0.4 |
0.3 |
13.9 |
1.4 |
18.0 |
442 |
1000 |
16x2x0.5 |
0.4 |
0.3 |
15.4 |
1.5 |
19.7 |
534 |
1000 |
20x2x0.5 |
0.4 |
0.3 |
17.1 |
1.5 |
21.5 |
607 |
1000 |
24x2x0.5 |
0.4 |
0.3 |
19.0 |
1.6 |
23.6 |
711 |
1000 |
30x2x0.5 |
0.4 |
0.3 |
20.2 |
1.7 |
24.9 |
813 |
500 |
Conductor : 0.75 mm2 (7x0.37 mm) |
|||||||
1x2x0.75 |
0.5 |
0.2 |
6.5 |
1.1 |
9.6 |
133 |
1000 |
2x2x0.75 |
0.5 |
0.2 |
9.2 |
1.2 |
12.5 |
199 |
1000 |
3x2x0.75 |
0.5 |
0.2 |
9.8 |
1.2 |
13.1 |
224 |
1000 |
4x2x0.75 |
0.5 |
0.3 |
10.7 |
1.3 |
14.6 |
290 |
1000 |
5x2x0.75 |
0.5 |
0.3 |
11.6 |
1.3 |
15.6 |
335 |
1000 |
6x2x0.75 |
0.5 |
0.3 |
12.7 |
1.4 |
16.8 |
375 |
1000 |
7x2x0.75 |
0.5 |
0.3 |
12.7 |
1.4 |
16.8 |
394 |
1000 |
10x2x0.75 |
0.5 |
0.3 |
16.1 |
1.5 |
20.5 |
534 |
1000 |
12x2x0.75 |
0.5 |
0.3 |
16.7 |
1.5 |
21.0 |
580 |
1000 |
16x2x0.75 |
0.5 |
0.3 |
18.6 |
1.6 |
23.1 |
711 |
1000 |
20x2x0.75 |
0.5 |
0.3 |
20.7 |
1.7 |
25.5 |
828 |
500 |
24x2x0.75 |
0.5 |
0.3 |
23.1 |
1.8 |
28.0 |
969 |
500 |
30x2x0.75 |
0.5 |
0.3 |
24.5 |
1.8 |
29.4 |
1105 |
500 |
|
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 2.5 mm2 (7x0.67 mm) |
|||||||
1x2x2.5 |
0.6 |
0.2 |
8.7 |
1.2 |
12.0 |
208 |
1000 |
2x2x2.5 |
0.6 |
0.3 |
12.8 |
1.4 |
17.0 |
371 |
1000 |
3x2x2.5 |
0.6 |
0.3 |
13.7 |
1.4 |
17.8 |
454 |
1000 |
4x2x2.5 |
0.6 |
0.3 |
15.0 |
1.4 |
19.2 |
522 |
1000 |
5x2x2.5 |
0.6 |
0.3 |
16.5 |
1.5 |
20.9 |
626 |
1000 |
6x2x2.5 |
0.6 |
0.3 |
18.1 |
1.6 |
22.6 |
713 |
1000 |
7x2x2.5 |
0.6 |
0.3 |
18.1 |
1.6 |
22.6 |
769 |
1000 |
10x2x2.5 |
0.6 |
0.3 |
23.3 |
1.8 |
28.3 |
1074 |
500 |
12x2x2.5 |
0.6 |
0.3 |
24.2 |
1.8 |
29.1 |
1199 |
500 |
16x2x2.5 |
0.6 |
0.3 |
27.0 |
1.9 |
32.2 |
1501 |
500 |
20x2x2.5 |
0.6 |
0.3 |
30.7 |
2.0 |
36.1 |
1846 |
500 |
24x2x2.5 |
0.6 |
0.4 |
34.3 |
2.2 |
40.5 |
2263 |
500 |
30x2x2.5 |
0.6 |
0.4 |
36.4 |
2.3 |
42.8 |
2700 |
500 |

|