N2XSEYKYRY

3.6/6 kV (IEC 60502 - 2)

Nominal cross section area of conductor

Conductor Diamater

Insulation thickness

Diameter Under Armour

Armour Wire Diameter

Diameter Over Lead Sheath

Lead Sheath Thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

mm

mm

mm

mm

mm

Kg/Km

meter

3x25 rm/16

5.8

2.5

40.7

2.5

38.1

1.7

2.5

50.7

6831

1000

3x35 rm/16

7.0

2.5

43.4

2.5

40.6

1.7

2.6

53.6

7607

1000

3x50 rm/16

8.2

2.5

46.6

2.5

43.8

1.8

2.7

57.0

8766

500

3x70 rm/16

9.9

2.5

50.7

2.5

47.7

1.9

2.8

61.3

10246

250

3x95 rm/16

11.5

2.5

54.5

2.5

51.3

2.0

3.0

65.5

11858

250

3x120 rm/16

13.0

2.5

58.3

2.5

55.1

2.1

3.1

69.5

13542

250

3x150 rm/25

14.5

2.5

62.0

3.2

58.6

2.2

3.2

74.7

16170

250

3x185 rm/25

16.1

2.5

66.7

3.2

63.1

2.3

3.4

79.8

18530

250

3x240 rm/25

18.5

2.6

72.9

3.2

69.1

2.5

3.6

86.4

21950

250

6/10 kV (IEC 60502 - 2)

Nominal cross section area of conductor

Conductor Diamater

Insulation thickness

Diameter Under Armour

Armour Wire Diameter

Diameter Over Lead Sheath

Lead Sheath Thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

mm

mm

mm

mm

mm

Kg/Km

meter

3x25 rm/16

5.8

3.4

44.9

2.5

42.1

1.8

2.7

55.3

7820

500

3x35 rm/16

7.0

3.4

47.9

2.5

45.1

1.8

2.7

58.3

8650

500

3x50 rm/16

8.2

3.4

50.9

2.5

47.9

1.9

2.9

61.7

9842

500

3x70 rm/16

9.9

3.4

55.5

2.5

52.3

2.1

3.1

66.7

11679

250

3x95 rm/16

11.5

3.4

59.0

2.5

55.8

2.1

3.1

70.2

13079

250

3x120 rm/16

13.0

3.4

62.6

3.2

59.2

2.2

3.3

75.5

15686

250

3x150 rm/25

14.5

3.4

66.2

3.2

62.6

2.3

3.4

79.3

17538

250

3x185 rm/25

16.1

3.4

70.9

3.2

67.1

2.4

3.5

84.2

19929

250

3x240 rm/25

18.5

3.4

77.3

3.2

73.3

2.7

3.8

91.2

23558

250

8.7/15 kV (IEC 60502 - 2)

Nominal cross section area of conductor

Conductor Diamater

Insulation thickness

Diameter Under Armour

Armour Wire Diameter

Diameter Over Lead Sheath

Lead Sheath Thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

mm

mm

mm

mm

mm

Kg/Km

meter

3x25 rm/16

5.8

4.5

50.5

2.5

47.5

1.9

2.8

61.1

9207

500

3x35 rm/16

7.0

4.5

53.2

2.5

50.2

2.0

2.9

64.0

10259

250

3x50 rm/16

8.2

4.5

56.2

2.5

53.0

2.1

3.0

67.2

11460

250

3x70 rm/16

9.9

4.5

60.7

3.2

57.3

2.2

3.2

73.4

14106

250

3x95 rm/16

11.5

4.5

64.3

3.2

60.9

2.3

3.3

77.2

15682

250

3x120 rm/16

13.0

4.5

67.9

3.2

64.3

2.4

3.5

81.2

17539

250

3x150 rm/25

14.5

4.5

71.6

3.2

67.8

2.5

3.6

85.1

19468

250

3x185 rm/25

16.1

4.5

76.7

3.2

72.7

2.6

3.8

90.6

21914

250

3x240 rm/25

18.5

4.5

82.2

4.0

78.0

2.7

4.0

98.2

26906

250

12/20 kV (IEC 60502 - 2)

Nominal cross section area of conductor

Conductor Diamater

Insulation thickness

Diameter Under Armour

Armour Wire Diameter

Diameter Over Lead Sheath

Lead Sheath Thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

mm

mm

mm

mm

mm

Kg/Km

meter

3x25 rm/16

5.8

5.5

55.4

2.5

52.2

2.1

3.0

66.4

10542

250

3x35 rm/16

7.0

5.5

58.7

2.5

55.3

2.2

3.2

70.1

11791

250

3x50 rm/16

8.2

5.5

61.7

3.2

58.1

2.3

3.4

74.8

13987

250

3x70 rm/16

9.9

5.5

65.6

3.2

62.0

2.4

3.5

78.9

15827

250

3x95 rm/16

11.5

5.5

69.0

3.2

65.4

2.4

3.5

82.3

17250

250

3x120 rm/16

13.0

5.5

72.6

3.2

68.8

2.5

3.6

86.1

19067

250

3x150 rm/25

14.5

5.5

76.7

4.0

72.7

2.6

3.8

92.3

22592

250

3x185 rm/25

16.1

5.5

81.2

4.0

77.2

2.7

4.0

97.2

25258

250

3x240 rm/25

18.5

5.5

86.7

4.0

82.5

2.8

4.1

102.9

28667

250