TiMF
|
Criteria |
Standard Values |
Unit |
||||
Conductor cross section |
Nominal |
0.5 |
0.75 |
1 |
1.5 |
2.5 |
mm² |
Conductor DC Resistance @ 20oC |
max. |
36.7 |
25.0 |
18.5 |
12.3 |
7.4 |
Ohm/kM |
Insulation resistance |
min. |
1000 |
MOhm x km |
||||
Mutual capacitance |
max. |
150 |
nF/km |
||||
Capacitance unbalance |
max. |
500 |
pF/500m |
||||
L/R (ratio) |
max. |
25 |
25 |
25 |
40 |
60 |
microH/Ohm |
Test voltage : |
for 1 minute |
2.0 kV A.C or 3.0 kV D.C |
K.V |
||||
core to core |
|||||||
core to screen |
|||||||
Operating voltage U(rms) |
|
500 |
V |
Nominal cross section area of conductor |
Insulation thickness |
Armour Tape Thickness |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 0.5 mm2 (7x0.30 mm) |
|||||||
1x3x0.5 |
0.6 |
0.2 |
8.2 |
1.3 |
11.6 |
197 |
1000 |
2x3x0.5 |
0.6 |
0.2 |
13.4 |
1.4 |
17.0 |
331 |
1000 |
3x3x0.5 |
0.6 |
0.2 |
14.3 |
1.4 |
17.9 |
384 |
1000 |
4x3x0.5 |
0.6 |
0.2 |
15.8 |
1.5 |
19.6 |
455 |
1000 |
5x3x0.5 |
0.6 |
0.2 |
17.3 |
1.5 |
21.1 |
520 |
1000 |
6x3x0.5 |
0.6 |
0.2 |
19.0 |
1.5 |
22.8 |
588 |
1000 |
7x3x0.5 |
0.6 |
0.2 |
19.0 |
1.5 |
22.8 |
626 |
1000 |
10x3x0.5 |
0.6 |
0.2 |
24.6 |
1.7 |
28.8 |
859 |
500 |
12x3x0.5 |
0.6 |
0.2 |
25.5 |
1.7 |
29.7 |
951 |
500 |
16x3x0.5 |
0.6 |
0.2 |
28.5 |
1.7 |
32.7 |
1159 |
500 |
20x3x0.5 |
0.6 |
0.2 |
32.0 |
1.8 |
36.4 |
1388 |
500 |
24x3x0.5 |
0.6 |
0.2 |
36.1 |
1.9 |
40.7 |
1664 |
500 |
30x3x0.5 |
0.6 |
0.2 |
38.4 |
1.9 |
43.0 |
1937 |
500 |
Conductor : 0.75 mm2 (7x0.37 mm) |
|||||||
1x3x0.75 |
0.6 |
0.2 |
8.7 |
1.3 |
12.1 |
215 |
1000 |
2x3x0.75 |
0.6 |
0.2 |
14.3 |
1.4 |
17.9 |
365 |
1000 |
3x3x0.75 |
0.6 |
0.2 |
15.2 |
1.5 |
19.0 |
437 |
1000 |
4x3x0.75 |
0.6 |
0.2 |
16.8 |
1.5 |
20.6 |
512 |
1000 |
5x3x0.75 |
0.6 |
0.2 |
18.5 |
1.5 |
22.3 |
589 |
1000 |
6x3x0.75 |
0.6 |
0.2 |
20.3 |
1.6 |
24.3 |
678 |
1000 |
7x3x0.75 |
0.6 |
0.2 |
20.3 |
1.6 |
24.3 |
725 |
1000 |
10x3x0.75 |
0.6 |
0.2 |
26.3 |
1.7 |
30.5 |
987 |
500 |
12x3x0.75 |
0.6 |
0.2 |
27.2 |
1.7 |
31.4 |
1099 |
500 |
16x3x0.75 |
0.6 |
0.2 |
30.5 |
1.8 |
34.9 |
1362 |
500 |
20x3x0.75 |
0.6 |
0.2 |
34.3 |
1.9 |
38.9 |
1636 |
500 |
24x3x0.75 |
0.6 |
0.2 |
38.7 |
2.0 |
43.5 |
1960 |
500 |
30x3x0.75 |
0.6 |
0.5 |
41.1 |
2.0 |
47.1 |
2786 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 1.0 mm2 (7x0.43 mm) |
|||||||
1x3x1 |
0.6 |
0.2 |
9.1 |
1.3 |
12.5 |
230 |
1000 |
2x3x1 |
0.6 |
0.2 |
15.0 |
1.5 |
18.8 |
403 |
1000 |
3x3x1 |
0.6 |
0.2 |
16.0 |
1.5 |
19.8 |
477 |
1000 |
4x3x1 |
0.6 |
0.2 |
17.7 |
1.5 |
21.5 |
563 |
1000 |
5x3x1 |
0.6 |
0.2 |
19.5 |
1.5 |
23.3 |
651 |
1000 |
6x3x1 |
0.6 |
0.2 |
21.4 |
1.6 |
25.4 |
751 |
500 |
7x3x1 |
0.6 |
0.2 |
21.4 |
1.6 |
25.4 |
808 |
500 |
10x3x1 |
0.6 |
0.2 |
27.7 |
1.7 |
31.9 |
1104 |
500 |
12x3x1 |
0.6 |
0.2 |
28.8 |
1.7 |
33.0 |
1236 |
500 |
16x3x1 |
0.6 |
0.2 |
32.2 |
1.8 |
36.6 |
1539 |
500 |
20x3x1 |
0.6 |
0.2 |
36.6 |
1.9 |
41.2 |
1895 |
500 |
24x3x1 |
0.6 |
0.5 |
40.9 |
2.0 |
46.9 |
2711 |
500 |
30x3x1 |
0.6 |
0.5 |
43.5 |
2.1 |
49.7 |
3151 |
500 |
Conductor : 1.5 mm2 (7x0.53 mm) |
|||||||
1x3x1.5 |
0.6 |
0.2 |
9.7 |
1.4 |
13.3 |
266 |
1000 |
2x3x1.5 |
0.6 |
0.2 |
16.2 |
1.5 |
20.0 |
462 |
1000 |
3x3x1.5 |
0.6 |
0.2 |
17.3 |
1.5 |
21.1 |
556 |
1000 |
4x3x1.5 |
0.6 |
0.2 |
19.2 |
1.6 |
23.2 |
672 |
1000 |
5x3x1.5 |
0.6 |
0.2 |
21.1 |
1.6 |
25.1 |
782 |
500 |
6x3x1.5 |
0.6 |
0.2 |
23.2 |
1.6 |
27.2 |
895 |
500 |
7x3x1.5 |
0.6 |
0.2 |
23.2 |
1.6 |
27.2 |
969 |
500 |
10x3x1.5 |
0.6 |
0.2 |
30.2 |
1.8 |
34.6 |
1345 |
500 |
12x3x1.5 |
0.6 |
0.2 |
31.3 |
1.8 |
35.7 |
1515 |
500 |
16x3x1.5 |
0.6 |
0.2 |
35.4 |
1.9 |
40.0 |
1937 |
500 |
20x3x1.5 |
0.6 |
0.5 |
39.8 |
2.0 |
45.8 |
2817 |
500 |
24x3x1.5 |
0.6 |
0.5 |
44.5 |
2.1 |
50.7 |
3282 |
250 |
30x3x1.5 |
0.6 |
0.5 |
47.4 |
2.2 |
53.8 |
3840 |
250 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 2.5 mm2 (7x0.67 mm) |
|||||||
1x3x2.5 |
0.7 |
0.2 |
11.1 |
1.4 |
14.7 |
325 |
1000 |
2x3x2.5 |
0.7 |
0.2 |
18.7 |
1.6 |
22.7 |
587 |
1000 |
3x3x2.5 |
0.7 |
0.2 |
20.1 |
1.6 |
24.1 |
719 |
1000 |
4x3x2.5 |
0.7 |
0.2 |
22.2 |
1.6 |
26.2 |
867 |
500 |
5x3x2.5 |
0.7 |
0.2 |
24.5 |
1.7 |
28.7 |
1029 |
500 |
6x3x2.5 |
0.7 |
0.2 |
27.0 |
1.7 |
31.2 |
1183 |
500 |
7x3x2.5 |
0.7 |
0.2 |
27.0 |
1.7 |
31.2 |
1292 |
500 |
10x3x2.5 |
0.7 |
0.2 |
35.6 |
1.9 |
40.2 |
1840 |
500 |
12x3x2.5 |
0.7 |
0.2 |
36.9 |
2.0 |
41.7 |
2099 |
500 |
16x3x2.5 |
0.7 |
0.5 |
41.4 |
2.1 |
47.6 |
3137 |
500 |
20x3x2.5 |
0.7 |
0.5 |
46.9 |
2.2 |
53.3 |
3813 |
250 |
24x3x2.5 |
0.7 |
0.5 |
52.5 |
2.3 |
59.1 |
4454 |
250 |
30x3x2.5 |
0.7 |
0.5 |
55.8 |
2.4 |
62.6 |
5242 |
250 |

|