نمایش منو

Multi-Core

 

Criteria

Standard Values

Unit

Conductor cross section

Nominal

0.5

0.75

1

1.5

2.5

mm²

Conductor DC Resistance @ 20oC

max.

36.7

25.0

18.5

12.3

7.4

Ohm/kM

Insulation resistance

min.

1000

MOhm x km

Mutual capacitance

max.

150

nF/km

Capacitance unbalance

max.

500

pF/500m

L/R (ratio)

max.

25

25

25

40

60

microH/Ohm

Test voltage :

for 1 minute

2.0 kV A.C or 3.0 kV D.C

K.V

core to core

core to screen

Operating voltage U(rms)

 

500

V

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 0.5 mm2 (7x0.3 mm)

2x0.5

0.6

0.9

7.2

48

1000

3x0.5

0.6

0.9

7.7

58

1000

4x0.5

0.6

0.9

8.3

70

1000

5x0.5

0.6

0.9

9.1

82

1000

6x0.5

0.6

0.9

9.8

94

1000

7x0.5

0.6

0.9

9.8

104

1000

8x0.5

0.6

1.0

11.6

123

1000

10x0.5

0.6

1.0

12.6

146

1000

12x0.5

0.6

1.0

13.0

166

1000

16x0.5

0.6

1.1

14.6

214

1000

20x0.5

0.6

1.1

16.2

259

1000

24x0.5

0.6

1.2

18.2

310

1000

30x0.5

0.6

1.2

19.2

371

1000

Conductor : 0.75 mm2 (7x0.37 mm)

2x0.75

0.6

0.9

7.7

55

1000

3x0.75

0.6

0.9

8.1

69

1000

4x0.75

0.6

0.9

8.8

84

1000

5x0.75

0.6

0.9

9.6

99

1000

6x0.75

0.6

1.0

10.7

119

1000

7x0.75

0.6

1.0

10.7

131

1000

8x0.75

0.6

1.0

12.3

150

1000

10x0.75

0.6

1.1

13.6

184

1000

12x0.75

0.6

1.1

14.1

211

1000

16x0.75

0.6

1.1

15.6

267

1000

20x0.75

0.6

1.2

17.6

330

1000

24x0.75

0.6

1.2

19.4

388

1000

30x0.75

0.6

1.3

20.8

475

1000

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 1.0 mm2 (7x0.43 mm)

2x1

0.6

0.9

8.0

62

1000

3x1

0.6

0.9

8.5

79

1000

4x1

0.6

0.9

9.3

97

1000

5x1

0.6

1.0

10.3

119

1000

6x1

0.6

1.0

11.2

138

1000

7x1

0.6

1.0

11.2

153

1000

8x1

0.6

1.0

13.0

175

1000

10x1

0.6

1.1

14.4

216

1000

12x1

0.6

1.1

14.8

248

1000

16x1

0.6

1.1

16.4

316

1000

20x1

0.6

1.2

18.5

392

1000

24x1

0.6

1.2

20.5

462

1000

30x1

0.6

1.3

21.9

567

1000

Conductor : 1.5 mm2 (7x0.53 mm)

2x1.5

0.6

0.9

8.6

76

1000

3x1.5

0.6

0.9

9.2

99

1000

4x1.5

0.6

1.0

10.2

127

1000

5x1.5

0.6

1.0

11.1

152

1000

6x1.5

0.6

1.0

12.1

176

1000

7x1.5

0.6

1.0

12.1

197

1000

8x1.5

0.6

1.1

14.3

231

1000

10x1.5

0.6

1.1

15.6

279

1000

12x1.5

0.6

1.1

16.1

323

1000

16x1.5

0.6

1.2

18.1

421

1000

20x1.5

0.6

1.2

20.1

514

1000

24x1.5

0.6

1.3

22.5

616

1000

30x1.5

0.6

1.4

24.0

757

1000

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 2.5 mm2 (7x0.67 mm)

2x2.5

0.7

1.0

10.1

107

1000

3x2.5

0.7

1.0

10.7

141

1000

4x2.5

0.7

1.0

11.7

177

1000

5x2.5

0.7

1.1

13.0

218

1000

6x2.5

0.7

1.1

14.2

255

1000

7x2.5

0.7

1.1

14.2

287

1000

8x2.5

0.7

1.2

16.7

335

1000

10x2.5

0.7

1.2

18.2

406

1000

12x2.5

0.7

1.2

18.9

472

1000

16x2.5

0.7

1.3

21.2

617

1000

20x2.5

0.7

1.4

23.8

765

1000

24x2.5

0.7

1.5

26.6

916

500

30x2.5

0.7

1.5

28.2

1115

500