نمایش منو

Multi-Core

 

Criteria

Standard Values

Unit

Conductor cross section

Nominal

0.5

0.75

1

1.5

2.5

mm²

Conductor DC Resistance @ 20oC

max.

40.4

26

19.2

12.8

7.86

Ohm/kM

Insulation resistance

min.

100

MOhm x km

Mutual capacitance

max.

250

nF/km

L/R (ratio)

max.

25

25

25

40

60

microH/Ohm

Test voltage :

for 5 minutes

1.5 kV A.C

K.V

core to core

core to screen

Operating voltage U(rms)

 

300

V

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 0.5 mm2 (7x0.3 mm)

2x0.5

0.6

1.0

7.0

65

1000

3x0.5

0.6

1.0

7.4

76

1000

4x0.5

0.6

1.0

7.9

91

1000

5x0.5

0.6

1.1

8.7

110

1000

6x0.5

0.6

1.1

9.3

123

1000

7x0.5

0.6

1.1

9.3

131

1000

8x0.5

0.6

1.1

10.6

151

1000

10x0.5

0.6

1.2

11.6

178

1000

12x0.5

0.6

1.2

12.0

198

1000

16x0.5

0.6

1.2

13.3

266

1000

20x0.5

0.6

1.3

14.8

324

1000

24x0.5

0.6

1.4

16.4

377

1000

30x0.5

0.6

1.4

17.3

443

1000

Conductor : 0.75 mm2 (7x0.37 mm)

2x0.75

0.6

1.0

7.4

73

1000

3x0.75

0.6

1.0

7.8

91

1000

4x0.75

0.6

1.1

8.6

109

1000

5x0.75

0.6

1.1

9.3

129

1000

6x0.75

0.6

1.1

9.9

148

1000

7x0.75

0.6

1.1

9.9

160

1000

8x0.75

0.6

1.2

11.5

185

1000

10x0.75

0.6

1.2

12.7

233

1000

12x0.75

0.6

1.2

13.1

266

1000

16x0.75

0.6

1.3

14.5

328

1000

20x0.75

0.6

1.3

16.0

392

1000

24x0.75

0.6

1.4

17.7

466

1000

30x0.75

0.6

1.4

18.9

577

1000

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 1.0 mm2 (7x0.43 mm)

2x1

0.6

1.0

7.8

85

1000

3x1

0.6

1.0

8.2

102

1000

4x1

0.6

1.1

9.0

128

1000

5x1

0.6

1.1

9.7

146

1000

6x1

0.6

1.1

10.5

169

1000

7x1

0.6

1.1

10.5

184

1000

8x1

0.6

1.2

12.4

231

1000

10x1

0.6

1.2

13.4

274

1000

12x1

0.6

1.2

13.8

307

1000

16x1

0.6

1.3

15.3

389

1000

20x1

0.6

1.4

17.1

474

1000

24x1

0.6

1.4

19.0

580

1000

30x1

0.6

1.5

20.2

686

1000

Conductor : 1.5 mm2 (7x0.53 mm)

2x1.5

0.7

1.1

9.0

112

1000

3x1.5

0.7

1.1

9.5

137

1000

4x1.5

0.7

1.1

10.3

167

1000

5x1.5

0.7

1.2

11.3

198

1000

6x1.5

0.7

1.2

12.4

245

1000

7x1.5

0.7

1.2

12.4

267

1000

8x1.5

0.7

1.3

14.4

314

1000

10x1.5

0.7

1.3

15.6

373

1000

12x1.5

0.7

1.3

16.1

420

1000

16x1.5

0.7

1.4

17.9

535

1000

20x1.5

0.7

1.5

20.2

681

1000

24x1.5

0.7

1.6

22.4

809

1000

30x1.5

0.7

1.6

23.6

953

1000

Nominal cross section area of conductor

Insulation thickness

Sheath thickness

Overall Diameter

Weight

Standard Packing Length

mm2

mm

mm

mm

Kg/Km

meter

Conductor : 2.5 mm2 (7x0.67 mm)

2x2.5

0.7

1.1

9.8

141

1000

3x2.5

0.7

1.1

10.4

176

1000

4x2.5

0.7

1.2

11.5

218

1000

5x2.5

0.7

1.2

12.7

275

1000

6x2.5

0.7

1.2

13.7

320

1000

7x2.5

0.7

1.2

13.7

352

1000

8x2.5

0.7

1.3

15.9

412

1000

10x2.5

0.7

1.4

17.5

502

1000

12x2.5

0.7

1.4

18.0

570

1000

16x2.5

0.7

1.5

20.3

755

1000

20x2.5

0.7

1.6

22.6

926

1000

24x2.5

0.7

1.6

24.9

1084

500

30x2.5

0.7

1.7

26.5

1303

500