TiMF
|
Criteria |
Standard Values |
Unit |
||||
Conductor cross section |
Nominal |
0.5 |
0.75 |
1 |
1.5 |
2.5 |
mm² |
Conductor DC Resistance @ 20oC |
max. |
36.7 |
25.0 |
18.5 |
12.3 |
7.4 |
Ohm/kM |
Insulation resistance |
min. |
1000 |
MOhm x km |
||||
Mutual capacitance |
max. |
150 |
nF/km |
||||
Capacitance unbalance |
max. |
500 |
pF/500m |
||||
L/R (ratio) |
max. |
25 |
25 |
25 |
40 |
60 |
microH/Ohm |
Test voltage : |
for 1 minute |
2.0 kV A.C or 3.0 kV D.C |
K.V |
||||
core to core |
|||||||
core to screen |
|||||||
Operating voltage U(rms) |
|
500 |
V |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 0.5 mm2 (7x0.30 mm) |
|||||||
1x3x0.5 |
0.6 |
0.9 |
12.3 |
1.4 |
16.9 |
466 |
1000 |
2x3x0.5 |
0.6 |
1.25 |
16.6 |
1.5 |
22.1 |
790 |
1000 |
3x3x0.5 |
0.6 |
1.25 |
17.3 |
1.6 |
23.0 |
864 |
1000 |
4x3x0.5 |
0.6 |
1.25 |
18.5 |
1.6 |
24.2 |
949 |
1000 |
5x3x0.5 |
0.6 |
1.25 |
19.8 |
1.6 |
25.5 |
1035 |
500 |
6x3x0.5 |
0.6 |
1.25 |
21.2 |
1.6 |
26.9 |
1123 |
500 |
7x3x0.5 |
0.6 |
1.25 |
21.2 |
1.6 |
26.9 |
1154 |
500 |
10x3x0.5 |
0.6 |
1.6 |
25.8 |
1.8 |
32.6 |
1676 |
500 |
12x3x0.5 |
0.6 |
1.6 |
26.5 |
1.8 |
33.3 |
1769 |
500 |
16x3x0.5 |
0.6 |
2 |
29.0 |
1.9 |
36.8 |
2293 |
500 |
20x3x0.5 |
0.6 |
2 |
31.9 |
1.9 |
39.7 |
2579 |
500 |
24x3x0.5 |
0.6 |
2.5 |
35.4 |
2.0 |
44.4 |
3354 |
500 |
30x3x0.5 |
0.6 |
2.5 |
37.3 |
2.1 |
46.5 |
3679 |
500 |
Conductor : 0.75 mm2 (7x0.37 mm) |
|||||||
1x3x0.75 |
0.6 |
0.9 |
12.8 |
1.4 |
17.4 |
495 |
1000 |
2x3x0.75 |
0.6 |
1.25 |
17.5 |
1.6 |
23.2 |
855 |
1000 |
3x3x0.75 |
0.6 |
1.25 |
18.3 |
1.6 |
24.0 |
931 |
1000 |
4x3x0.75 |
0.6 |
1.25 |
19.6 |
1.6 |
25.3 |
1026 |
500 |
5x3x0.75 |
0.6 |
1.25 |
21.0 |
1.6 |
26.7 |
1124 |
500 |
6x3x0.75 |
0.6 |
1.6 |
22.5 |
1.7 |
29.1 |
1413 |
500 |
7x3x0.75 |
0.6 |
1.6 |
22.5 |
1.7 |
29.1 |
1453 |
500 |
10x3x0.75 |
0.6 |
1.6 |
27.5 |
1.8 |
34.3 |
1852 |
500 |
12x3x0.75 |
0.6 |
2 |
28.3 |
1.8 |
35.9 |
2225 |
500 |
16x3x0.75 |
0.6 |
2 |
31.0 |
1.9 |
38.8 |
2557 |
500 |
20x3x0.75 |
0.6 |
2 |
34.6 |
2.0 |
42.6 |
2963 |
500 |
24x3x0.75 |
0.6 |
2.5 |
38.3 |
2.1 |
47.5 |
3793 |
500 |
30x3x0.75 |
0.6 |
2.5 |
40.4 |
2.2 |
49.8 |
4219 |
500 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 1.0 mm2 (7x0.43 mm) |
|||||||
1x3x1 |
0.6 |
0.9 |
13.1 |
1.4 |
17.7 |
515 |
1000 |
2x3x1 |
0.6 |
1.25 |
18.2 |
1.6 |
23.9 |
905 |
1000 |
3x3x1 |
0.6 |
1.25 |
19.0 |
1.6 |
24.7 |
991 |
500 |
4x3x1 |
0.6 |
1.25 |
20.4 |
1.6 |
26.1 |
1097 |
500 |
5x3x1 |
0.6 |
1.6 |
22.0 |
1.7 |
28.6 |
1388 |
500 |
6x3x1 |
0.6 |
1.6 |
23.6 |
1.7 |
30.2 |
1518 |
500 |
7x3x1 |
0.6 |
1.6 |
23.6 |
1.7 |
30.2 |
1567 |
500 |
10x3x1 |
0.6 |
2 |
29.0 |
1.9 |
36.8 |
2283 |
500 |
12x3x1 |
0.6 |
2 |
29.8 |
1.9 |
37.6 |
2424 |
500 |
16x3x1 |
0.6 |
2 |
32.7 |
1.9 |
40.5 |
2781 |
500 |
20x3x1 |
0.6 |
2.5 |
36.5 |
2.1 |
45.7 |
3667 |
500 |
24x3x1 |
0.6 |
2.5 |
40.5 |
2.1 |
49.7 |
4169 |
500 |
30x3x1 |
0.6 |
2.5 |
42.7 |
2.2 |
52.1 |
4611 |
250 |
Conductor : 1.5 mm2 (7x0.53 mm) |
|||||||
1x3x1.5 |
0.6 |
0.9 |
13.8 |
1.5 |
18.6 |
563 |
1000 |
2x3x1.5 |
0.6 |
1.25 |
19.4 |
1.6 |
25.1 |
997 |
500 |
3x3x1.5 |
0.6 |
1.25 |
20.4 |
1.6 |
26.1 |
1101 |
500 |
4x3x1.5 |
0.6 |
1.6 |
21.9 |
1.7 |
28.5 |
1411 |
500 |
5x3x1.5 |
0.6 |
1.6 |
23.6 |
1.7 |
30.2 |
1560 |
500 |
6x3x1.5 |
0.6 |
1.6 |
25.4 |
1.8 |
32.2 |
1741 |
500 |
7x3x1.5 |
0.6 |
1.6 |
25.4 |
1.8 |
32.2 |
1807 |
500 |
10x3x1.5 |
0.6 |
2 |
31.4 |
1.9 |
39.2 |
2589 |
500 |
12x3x1.5 |
0.6 |
2 |
32.4 |
1.9 |
40.2 |
2793 |
500 |
16x3x1.5 |
0.6 |
2.5 |
36.0 |
2.1 |
45.2 |
3704 |
500 |
20x3x1.5 |
0.6 |
2.5 |
40.2 |
2.2 |
49.6 |
4300 |
500 |
24x3x1.5 |
0.6 |
3.15 |
44.2 |
2.3 |
55.1 |
5496 |
250 |
30x3x1.5 |
0.6 |
3.15 |
47.0 |
2.4 |
58.1 |
6212 |
250 |
Nominal cross section area of conductor |
Insulation thickness |
Armour Wire Diameter |
Diameter Under Armour |
Sheath thickness |
Overall Diameter |
Weight |
Standard Packing Length |
mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
meter |
Conductor : 2.5 mm2 (7x0.67 mm) |
|||||||
1x3x2.5 |
0.7 |
0.9 |
15.1 |
1.5 |
19.9 |
650 |
1000 |
2x3x2.5 |
0.7 |
1.6 |
21.9 |
1.7 |
28.5 |
1349 |
500 |
3x3x2.5 |
0.7 |
1.6 |
23.1 |
1.7 |
29.7 |
1504 |
500 |
4x3x2.5 |
0.7 |
1.6 |
25.0 |
1.8 |
31.8 |
1719 |
500 |
5x3x2.5 |
0.7 |
1.6 |
27.0 |
1.8 |
33.8 |
1926 |
500 |
6x3x2.5 |
0.7 |
2 |
29.2 |
1.9 |
37.0 |
2405 |
500 |
7x3x2.5 |
0.7 |
2 |
29.2 |
1.9 |
37.0 |
2503 |
500 |
10x3x2.5 |
0.7 |
2.5 |
36.8 |
2.1 |
46.0 |
3705 |
500 |
12x3x2.5 |
0.7 |
2.5 |
38.4 |
2.1 |
47.6 |
4035 |
500 |
16x3x2.5 |
0.7 |
2.5 |
42.3 |
2.2 |
51.7 |
4743 |
250 |
20x3x2.5 |
0.7 |
3.15 |
47.3 |
2.4 |
58.4 |
6228 |
250 |
24x3x2.5 |
0.7 |
3.15 |
52.5 |
2.5 |
63.8 |
7125 |
250 |
30x3x2.5 |
0.7 |
3.15 |
55.5 |
2.6 |
67.0 |
8013 |
250 |

|