Earthing arrangements (Schematics)
TN-C System earthing TN-S System earthing
TN-C-S System earthing with PME TN-C-S System earthing with PNB
TT System earthing IT System earthing
Cost :
TN networks save the cost of a low-impedance earth connection at the site of each consumer. Such a connection (a buried metal structure) is required to provide protective earth in IT and TT systems.
TN-C networks save the cost of an additional conductor needed for separate N and PE connections. However, to mitigate the risk of broken neutrals, special cable types and lots of connections to earth are needed.
Application examples :
* Most of modern homes in Europe have a TN-C-S earthing system .
* Laboratory rooms, medical facilities, construction sites, repair workshops, mobile electrical installations, and other environments that are supplied via engine-generators where there is an increased risk of insulation faults, often use an IT earthing arrangement supplied from isolation transformers .
* In remote areas, where the cost of an additional PE conductor outweighs the cost of a local earth connection, TT networks are commonly used in some countries